Industrial
Depending on the type and configuration of your connected LoRaWAN device, you will get one or several values for Analog or contact. Please refer to your device manual.
Address (hex) | Address (dec) | Size | description | Unit | Data Type |
---|---|---|---|---|---|
0x2000 | 8192 | 2 | last payload timestamp | second | DATETIME |
0x2002 | 8194 | 1 | Analog A : type of channel A |
| U16 |
0x2003 | 8195 | 2 | value of Analog A channel | type 0 = mA/1000 | U32 |
0x2005 | 8197 | 1 | Analog B : type of channel B |
| U16 |
0x2006 | 8198 | 2 | value of Analog B channel | type 0 = mA/1000 | U32 |
0x2008 | 8200 | 2 | input 1 : count value |
| U32 |
0x200A | 8202 | 1 | input 1 : currentState |
| U16 |
0x200B | 8203 | 1 | input 1 : previousFrameState |
| U16 |
0x200C | 8204 | 2 | input 2 : count value |
| U32 |
0x200E | 8206 | 1 | input 2 : currentState |
| U16 |
0x200F | 8207 | 1 | input 2 : previousFrameState |
| U16 |
0x2010 | 8208 | 2 | input 3 : count value |
| U32 |
0x2012 | 8210 | 1 | input 3 : currentState |
| U16 |
0x2013 | 8211 | 1 | input 3 : previousFrameState |
| U16 |
0x2014 | 8212 | 2 | input 4 : count value |
| U32 |
0x2016 | 8214 | 1 | input 4 : currentState |
| U16 |
0x2017 | 8215 | 1 | input 4 : previousFrameState |
| U16 |
0x2018 | 8216 | 2 | input 5 : count value |
| U32 |
0x201A | 8218 | 1 | input 5 : currentState |
| U16 |
0x201B | 8219 | 1 | input 5 : previousFrameState |
| U16 |
0x201C | 8220 | 2 | input 6 : count value |
| U32 |
0x201E | 8222 | 1 | input 6 : currentState |
| U16 |
0x201F | 8223 | 1 | input 6 : previousFrameState |
| U16 |
0x2020 | 8224 | 2 | input 7 : count value |
| U32 |
0x2022 | 8226 | 1 | input 7 : currentState |
| U16 |
0x2023 | 8227 | 1 | input 7 : previousFrameState |
| U16 |
0x2024 | 8228 | 2 | input 8 : count value |
| U32 |
0x2026 | 8230 | 1 | input 8 : currentState |
| U16 |
0x2027 | 8231 | 1 | input 8 : previousFrameState |
| U16 |
0x2028 | 8232 | 2 | input 9 : count value |
| U32 |
0x202A | 8234 | 1 | input 9 : currentState |
| U16 |
0x202B | 8235 | 1 | input 9 : previousFrameState |
| U16 |
0x202C | 8236 | 2 | input 10 : count value |
| U32 |
0x202E | 8238 | 1 | input 10 : currentState |
| U16 |
0x202F | 8239 | 1 | input 10 : previousFrameState |
| U16 |
0x2100 | 8448 | 1 | output 1 : current state |
| U16 |
0x2101 | 8449 | 1 | output 1 : New state (write 0 or 1 value only) |
| U16 |
0x2104 | 8452 | 1 | output 2 : current state |
| U16 |
0x2105 | 8453 | 1 | output 2 : New state (write 0 or 1 value only) |
| U16 |
0x2108 | 8456 | 1 | output 3 : current state |
| U16 |
0x2109 | 8457 | 1 | output 3 : New state (write 0 or 1 value only) |
| U16 |
0x210C | 8460 | 1 | output 4 : current state |
| U16 |
0x210D | 8461 | 1 | output 4 : New state (write 0 or 1 value only) |
| U16 |