The FTP interface can be used for:
Updating the Software
Updating the configuration *
Support
NOTE: Multiples configuration's updates can be done simultaneously : (Those will be done in this order)
License update
Device update
Output update
If the license's check is KO, the product will not start.
Setup FTP client
Connect to µWiotys using a FTP client (ex: Filezilla)
Host: $IP_Address_µWiotys (by default:
192.168.1.100
)Port: 2222
Protocol: SFTP (SSH File Transfer Protocol)
Warning the response time of µWiotys' FTP can be a little bit long, especially on fixed IP.
If necessary, you should extend your FTP Client timeout to 60 seconds, see Application Example
Contact Wi6labs support team for user/password: support@wi6labs.com
End device configuration
LoRaWAN device provisioning on µWiotys can be done by FTP transfer.
First, create the configuration file with proper parameters and format then connect to µWiotys with FTP and copy the configuration file into the proper directory.
Configuration file
File name
The name of the devices configuration file can be: devices_update.json or devices_update_XXXXXXXX.json
where “XXXXXXXX” is the hardware serial number of the board (8 digits, upper case), it can be found on the web interface in the Overview ⇒ Information menu.
One or many devices can be add or deleted with the same update file. You can use µWiotys Online support interface to help create your update file.
Parameters for each device
Field | Mandatory | description | Possible value |
---|---|---|---|
uwiotys.state | yes | Required action | "add"/"delete"/"active" |
uwiotys.reference | yes | End device manufacturer reference | Manufacturer reference : see LoRaWAN Compatible Devices |
uwiotys.output_protocols.modbus.@modbus | yes | Modbus slave ID | 1 to 200 |
spn.activation_type | yes | End device activation type, only OTAA supported | "OTAA" |
spn.dev_eui | yes | String of 16 hexadecimal characters | "70B3D5E75E008888" |
spn.app_eui | yes | String of 16 hexadecimal characters | "70B3D5E75F600000" |
spn.app_key | yes | String of 32 hexadecimal characters | "78FF2CDE6D2C657F09981C3332096DF9" |
spn.dev_addr | no | For future use | |
spn.nwks_key | no | For future use | |
spn.apps_key | no | For future use | |
spn.end_device_parameters.rx_window | yes | End device rx windows | This parameters cannot be change |
spn.end_device_parameters.rx_frequency | yes | End device rx frequency | This parameters cannot be change |
spn.end_device_parameters.rx_datarate | yes | End device data rate | This parameters cannot be change |
spn.end_device_parameters.class | yes | End device class | A or C |
Configuration file will be rejected at first error, missing field or wrong parameters.
File format
The file format should be as follow, several device can be listed in the sensors table.
{ "sensors": [ { "uwiotys": { "state": "add", "reference": "50-70-139", "output_protocols": { "modbus": { "@modbus": 1 } } }, "spn": { "activation_type": "OTAA", "dev_eui": "70B3D5E75E008D35", "app_eui": "70B3D5E75F600000", "app_key": "725070411F8720932F4A56B6117D0638", "dev_addr": "", "nwks_key": "", "apps_key": "", "end_device_parameters": { "rx_window": 3, "rx_frequency": 869525000, "rx_datarate": 0, "class": "A" } } }, { "uwiotys": { "state": "add", "reference": "50-70-053", "output_protocols": { "modbus": { "@modbus": 2 } } }, "spn": { "activation_type": "OTAA", "dev_eui": "70B3D5E75E008888", "app_eui": "70B3D5E75F600000", "app_key": "78FF2CDE6D2C657F09981C3332096DF9", "dev_addr": "", "nwks_key": "", "apps_key": "", "end_device_parameters": { "rx_window": 3, "rx_frequency": 869525000, "rx_datarate": 0, "class": "A" } } } ] }
Upload configuration
Upload the configuration file
Copy the devices configuration file into the directory: /uwiotys/update_config/
Create an empty file named "reboot" in directory "/update/". You can reboot with this method or with the reboot web interface button
An electric reboot can corrupt the update process !
After few minutes
If the update failed, you will find information into the file: devices_updates_$DATE_ERROR.log
If the update success, the file the devices configuration file is deleted and you will find the file: devices_updates_$DATE_SUCCESS.log
The devices current configuration of µWiotys is available in the directory: /uwiotys/current_config/
The file format is the same as the devices configuration file, it can be used to remove device for µWiotys config by simply changing "state" from "active" to "remove" for one or several devices and then follow the regular update procedure.
Output configuration
Configuration file
File name
The name of the output configuration file can be: output_update.json or output_update_XXXXXXXX.json
“XXXXXXXX” is the hardware serial number of the board (8 digits, upper case), it can be found on web interface in the Overview ⇒ Information menu.
Parameters
Field | Mandatory | description | Possible value |
---|---|---|---|
http_data_server.active | yes | activation status of the HTTP output, if activated all device data will be sent to HTTP server, if not no messages will be sent. This does impact modbus output | true / false |
http_data_server.url | yes | url of the external server, it must be accessible from the network of the GW | valid URL |
http_data_server.headers | yes | header information for the server | valid key / value list |
csv.active | yes | activation status of the csv output, if activated all device data be stored in csv files. This does impact modbus output | true / false |
csv.nb_week | yes | Number of week the csv files will be keep. Be careful not to keep the files too long so as not to saturate the storage space | [1:52] |
mqtt.active | yes | activation status of the mqtt output. This does impact modbus output | true / false |
mqtt.host | yes | External Mqtt Broker | valid host |
Http output support both http and https protocols. Mqtt output support both mqtt and mqtts protocols. IN both cases, auto signed certificate are not suppoerted.
File format
The file format should be as the following examples:
{ "http_data_server": { "active": true, "url": "https://webhook.site/102211e8-f30f-4117-82fa-999e1fd47caa", "headers": {} }, "csv":{ "active": true, "nb_week": 15 }, "mqtt":{ "active": true, "host": "mqtt.uWiotys.io", "port": 1883, "topic": "MyTopic", "login": "", "password": "", "secure(TLS)": false } }
{ "http_data_server": { "active": false, "url": "http://MyHTTPServer:8080", "headers": { "Content-Type": "application/x-www-form-urlencoded", "Authorization": "Bearer eyJhbGciOiJSUzI1NiIsInR5cCIgOiAiSldUIiwia2lkIiA6ICJBTDBERmROLW1DNFpMTFJCVXh4OFdxN1RNZTVmQ3NNSE1FV1FsUklNYmRjIn" } }, "csv":{ "active": true, "nb_week": 15 }, , "mqtt":{ "active": true, "host": "mqtt.uWiotys.io", "port": 8883, "topic": "MyTopic", "login": "MyLogin", "password": "MyPass", "secure(TLS)": true } }
Upload configuration
Upload the configuration file
See the process to add sensors for more details
An electric reboot can corrupt the update process
To test the HTTP configuration, µwiotys will send a test request with information about the Gateway (EUI, IP and MAC) and wait for a 200 OK response.
{ "EUI": "7076FF0056050190", "IP": "192.168.100.143", "MAC": "70:76:ff:03:02:e1" }
After a few seconds the LEDs stop blinking, wait another minute then reconnect you to the FTP. The status of the output configuration update can be found in /uwiotys/log/uwiotys_functionnal.log
Current configuration
The output current configuration of µWiotys is available in the directory: /uwiotys/current_config/
License Configuration
Configuration file
Where to get the license
See with Wi6labs if not already provided with the product.
File name
The license's file's name look like : license_XXXXXXXX.json. With "XXXXXXXX" as the hardware serial number.
Upload configuration
Upload the license
Same process than before, see Upload config and replace with the license_XXXXXXXX.json
How to know if the product has a license
You can find the information in the file : uwiotys/log/uwiotys_functional.log.
Logs can be :
"No license found, µWiotys will not start. Please configure a valid license for your µWiotys gateway XXXXXXXX" when NO license is present.
"The license is VALID. µWiotys will start." when the product have a license.
How to know the license's type and state
When the license is valid, you can find informations in the file : uwiotys/log/uwiotys_functional.log.
Logs can contain :
"Check license success. license type SIMPLE - C license in use, out of M license." for the SIMPLE license.
"Check license success. license type: LISTED : L" for the LISTED license.
With C as the currently used number of sensors, M as the maximum possible sensors' number.
And L as the list of authorized references.
How to know what outputs can be used with the current license
When the license is valid, you can find informations in the file : uwiotys/log/uwiotys_functional.log.
Logs contain :
License allow user to activate the following output: Modbus output: true/false Csv output: true/false Http output: true/false Mqtt output: true/false
Software Update
It is possible to update the installation of µwiotys to benefit from recent evolutions.
Updating files
Please contact Wi6labs support to get software files updates.
Update process
From 1.2.x to 1.3.0
Replace the XXXXXXX of the provided file :
XXXXXXXX_data.json
to be the 8 lasts digits of µwiotys' EUI.Push the renammed file to the configuration folder.
Check that a file (
XXXXXXXX_set_configuration_processed_ok
) is created in the configuration folder. (TIPS: Don't forget to refresh, if the file isn't created please reboot the GW and restart from step 1)Push the file : uwiotys-update_1.3.0_klkgw.ipk to the update folder.
Push the
update
file to the update folder.Check that a file (
XXXXXXXX_update_processed_ok
) is created in the update folder. (TIPS: Don't forget to refresh)Push the
reboot
file to the update folder.Check that a file (
XXXXXXXX_reboot_processed_yy
) is created in the update folder. (TIPS: Don't forget to refresh)Wait. (Take arround 5 minutes to complete)
If everything is ok, you must find in uwiotys/devices_current_config the following file :
devices_date-time.json
From 1.3.x to 2.x.x
Push the file : uwiotys-update_2.x.x.xxxx.ipk to the update folder.
Push the
update
file to the update folder.Check that a file (
XXXXXXXX_update_processed_ok
) is created in the update folder. (TIPS: Don't forget to refresh, if the file isn't created please reboot the GW and restart from step 1)Push the
reboot
file to the update folder.Check that a file (
XXXXXXXX_reboot_processed_yy
) is created in the update folder. (TIPS: Don't forget to refresh)Wait. (Take arround 5 minutes to complete)
Push the license to µwiotys, see how to in : Upload the license chapter.
If everything is ok, you must find in the last part of uwiotys/log/uwiotys_functional.log the following line :
The license is VALID. µWiotys will start.
From 2.x to 2.x and 3.x to 3.x
Warning upgration from 2.x to 3.x is not supported !
Push the file : uwiotys-update_2.x.x.xxxx.ipk to the update folder.
Push the
update
file to the update folder.Check that a file (
XXXXXXXX_update_processed_ok
) is created in the update folder. (TIPS: Don't forget to refresh, if the file isn't created please reboot the GW and restart from step 1)Push the
reboot
file to the update folder.Check that a file (
XXXXXXXX_reboot_processed_yy
) is created in the update folder. (TIPS: Don't forget to refresh)Wait. (Take arround 5 minutes to complete)
If everything is ok, you must find in the last part of uwiotys/log/uwiotys_functional.log the following line :
The license is VALID. µWiotys will start.
Note