In this example, we use FileZilla to configure the device and Modbus Doctor to read Modbus data from µWiotys

Connect your gateway

First, install your gateway with proper accessories according to your model and connect it to your local network.

You should be able to ping the gateway (default address is 192.168.1.100). If this is not possible, please make sure that the necessary ports are open. (Those are listed in Description)

GW.png

Configure your devices

Next, you need to create the configuration file (named devices_update.json) that contain necessary informations : Reference, DevEUI, AppKey, Modbus Slave address,...

You can check out our Online support interface to help you create your configuration file or FTP configuration for expert details.

Once your configuration is ready make sure to rename it devices_update.json.

config_tool.png

Push device configuration with FileZilla

It is now time to connect to your gateway using a FTP client (like, for instance, FileZilla)

  1. Open Site manager

  2. Create a new site

  3. Configure host with the gateway's IP

  4. Port is 2222

  5. Use SFTP protocol

  6. Enter User and Password

  7. You now should be able to connect to the gateway

fileZilla3.png

Warning!!! The answer time of µWiotys' FTP can be very long, especially on fixed IP. If necessary, you should extend FileZilla timeout to 60 seconds.

To do so : Edit → Settings

fileZilla2.png

Once connected to the FTP server, copy the devices configuration file devices_update.json (previously created) into the directory: /uwiotys/update_config/

After that, you need to reboot to process the device update.

See FTP configuration for more details.

Warning The LoRa device should only be started after the configuration is successfully done. µWiotys configuration must be valid before the device does a Join Request.

Read with Modbus Doctor

Configuration

TCP/IP IP address is µWiotys IP address Numport : 502 - Timeout : 1000.

To read Modbus device previously configured, select slave 5 in modbus doctor.

Get device configuration

Address

Size

Description

Type

0x0000

1

Modbus dictionary's version

uint16

0x0001

4

Device EUI

uint64

0x0005

1

Device Wi6labs reference ID

uint16

What you can see on Modbus Doctor:

read_config_modbus5.png

Get device Value

Address

Size

Description

Unit

Data Type

0x1000

2

last payload timestamp

second

U32

0x1002

1

Temperature 0

Celsius / 10

S16

0x1003

1

Humidity 0

% from 0 to 100

U16

What you can see on Modbus Doctor:

read_thr_modbus5.png

Real values:

Timestamps = 0x5FCDCF36 (word swapping) = 1 607 323 446 seconds = 7/12/2020 6:44:06
(check http://www.timestamp.fr/ for conversion example)

Temperature = 0xDE = 222 Celsius/10 = 22,2 °C

Humidity = 0x21 = 33 % of Humidity