Info |
---|
In this example, we use FileZilla to configure the device |
...
. |
Connect your gateway
First, install the gateway with proper accessories and connect it to your local network.
You should be able to ping the gateway (default address is 192.168.1.100).
If this is not possible, please make sure that the necessary ports are open. (Those are listed in Description)
...
Panel | ||||||||
---|---|---|---|---|---|---|---|---|
| ||||||||
! WARNING ! Please do NOT reset factory your gateway Before push the button, contact your saler to know the process |
Configure your devices
Next, you need to create the configuration file (named devices_update.json) that contains necessary informations : Reference, DevEUI, AppKey, Modbus Slave address,...
You can check out our Online support interface https://app.uwiotys.com/index.php/device/list to help you create your configuration file
or FTP configuration for expert details.
Once your configuration is ready make sure to rename it devices_update.json.
Panel | ||||||||
---|---|---|---|---|---|---|---|---|
| ||||||||
For BACnet : In the “Modbus address” you can choose any number for BACnet ID but it has to follow each other (if you want to start with 13 through 20, you have to set 13,14,15…20) in 3.4.0 (Corrected from 3.4.5) |
...
Push device configuration with FileZilla
...
Open Site manager
Create a new site
Configure host with the gateway's IP
Port is 2222
Use SFTP protocol
Enter User and Password
You now should be able to connect to the gateway
...
Note |
---|
Warning!!! The answer time of µWiotys' FTP can be very long, especially on fixed IP. If necessary, you should extend FileZilla timeout to 60 seconds. Don’t forget to refresh in order to see your current files |
To do so : Edit → Settings
...
Once connected to the FTP server, copy the devices configuration file devices_update.json (previously created) into the directory: /uwiotys/update_config/
...
See FTP configuration for more details.
Note |
---|
Warning The LoRa LoRaWAN device should only be started after the configuration is successfully done. |
Read
...
Configuration
TCP/IP IP address is µWiotys IP address Numport : 502 - Timeout : 1000.
To read Modbus device previously configured, select slave 5 in modbus doctor.
Get device configuration
...
Address
...
Size
...
Description
...
Type
...
0x0000
...
1
...
Modbus dictionary's version
...
uint16
...
0x0001
...
4
...
Device EUI
...
uint64
...
0x0005
...
1
...
Device Wi6labs reference ID
...
uint16
What you can see on Modbus Doctor:
...
Get device Value
...
Address
...
Size
...
Description
...
Unit
...
Data Type
...
0x1000
...
2
...
last payload timestamp
...
second
...
U32
...
0x1002
...
1
...
Temperature 0
...
Celsius / 10
...
S16
...
0x1003
...
1
...
Humidity 0
...
% from 0 to 100
...
U16
What you can see on Modbus Doctor:
...
Real values:
Timestamps = 0x5FCDCF36 (word swapping) = 1 607 323 446 seconds = 7/12/2020 6:44:06
(check http://www.timestamp.fr/ for conversion example)
Temperature = 0xDE = 222 Celsius/10 = 22,2 °C
...
sensors data (Modbus/BACnet)
Finally, you can see your device's data based on the µWiotys output protocol.