This table is dedicated for LoRaWAN to Modbus RTU RS485 devices. Please note that your LoRaWAN device must be configured with proper RS485 parameters matching your secondary BMS configuration : baud rate, parity, stop bit, data bits, slave, register address. Contact Wi6labs support for this initial configuration
Read RS485 Modbus registers with your LoRaWAN Device
Address (hex) | Address (dec) | Size | description | Unit | Data Type |
---|---|---|---|---|---|
5000 | 20480 | 2 | last payload timestamp | second | DATETIME |
5002 | 20482 | 1 | Identification of sensor Modbus frame | U16 | |
5003 | 20483 | 1 | Slave address | U16 | |
5004 | 20484 | 1 | RFU | U16 | |
5005 | 20485 | 1 | Datasize | U16 | |
5006 | 20486 | 1 | Modbus Fonction | U16 | |
5007 | 20487 | 1 | Alarm info: | U16 | |
5008 | 20488 | 2 | RFU | U32 | |
500A | 20490 | 125 | data read 1 | ByteField | |
5087 | 20615 | 2 | RFU | U32 | |
5089 | 20617 | 2 | last payload timestamp | DATETIME | |
508B | 20619 | 1 | Identification of sensor Modbus frame | U16 | |
508C | 20620 | 1 | Slave address | U16 | |
508D | 20621 | 1 | RFU | U16 | |
508E | 20622 | 1 | Datasize | U16 | |
508F | 20623 | 1 | Modbus Fonction | U16 | |
5090 | 20624 | 1 | Alarm info (alarm, up, down) | U16 | |
5091 | 20625 | 2 | RFU | U32 | |
5093 | 20627 | 125 | data read 2 | ByteField | |
5110 | 20752 | 2 | RFU | U32 | |
5112 | 20754 | 2 | last payload timestamp | DATETIME | |
5114 | 20756 | 1 | Identification of sensor Modbus frame | U16 | |
5115 | 20757 | 1 | Slave address | U16 | |
5116 | 20758 | 1 | RFU | U16 | |
5117 | 20759 | 1 | Datasize | U16 | |
5118 | 20760 | 1 | Modbus Fonction | U16 | |
5119 | 20761 | 1 | Alarm info (alarm, up, down) | U16 | |
511A | 20762 | 2 | RFU | U32 | |
511C | 20764 | 125 | data read 3 | ByteField | |
5199 | 20889 | 2 | RFU | U32 | |
519B | 20891 | 2 | last payload timestamp | DATETIME | |
519D | 20893 | 1 | Identification of sensor Modbus frame | U16 | |
519E | 20894 | 1 | Slave address | U16 | |
519F | 20895 | 1 | RFU | U16 | |
51A0 | 20896 | 1 | Datasize | U16 | |
51A1 | 20897 | 1 | Modbus Fonction | U16 | |
51A2 | 20898 | 1 | Alarm info (alarm, up, down) | U16 | |
51A3 | 20899 | 2 | RFU | U32 | |
51A5 | 20901 | 125 | data read 4 | ByteField | |
5222 | 21026 | 2 | RFU | U32 | |
5224 | 21028 | 2 | last payload timestamp | DATETIME | |
5226 | 21030 | 1 | Identification of sensor Modbus frame | U16 | |
5227 | 21031 | 1 | Slave address | U16 | |
5228 | 21032 | 1 | RFU | U16 | |
5229 | 21033 | 1 | Datasize | U16 | |
522A | 21034 | 1 | Modbus Fonction | U16 | |
522B | 21035 | 1 | Alarm info (alarm, up, down) | U16 | |
522C | 21036 | 2 | RFU | U32 | |
522E | 21038 | 125 | data read 5 | ByteField | |
52AB | 21163 | 2 | RFU | U32 | |
52AD | 21165 | 2 | last payload timestamp | DATETIME | |
52AF | 21167 | 1 | Identification of sensor Modbus frame | U16 | |
52B0 | 21168 | 1 | Slave address | U16 | |
52B1 | 21169 | 1 | RFU | U16 | |
52B2 | 21170 | 1 | Datasize | U16 | |
52B3 | 21171 | 1 | Modbus Fonction | U16 | |
52B4 | 21172 | 1 | Alarm info (alarm, up, down) | U16 | |
52B5 | 21173 | 2 | RFU | U32 | |
52B7 | 21175 | 125 | data read 6 | ByteField | |
5334 | 21300 | 2 | RFU | U32 | |
5336 | 21302 | 2 | last payload timestamp | DATETIME | |
5338 | 21304 | 1 | Identification of sensor Modbus frame | U16 | |
5339 | 21305 | 1 | Slave address | U16 | |
533A | 21306 | 1 | RFU | U16 | |
533B | 21307 | 1 | Datasize | U16 | |
533C | 21308 | 1 | Modbus Fonction | U16 | |
533D | 21309 | 1 | Alarm info (alarm, up, down) | U16 | |
533E | 21310 | 2 | RFU | U32 | |
5340 | 21312 | 125 | data read 7 | ByteField | |
53BD | 21437 | 2 | RFU | U32 | |
53BF | 21439 | 2 | last payload timestamp | DATETIME | |
53C1 | 21441 | 1 | Identification of sensor Modbus frame | U16 | |
53C2 | 21442 | 1 | Slave address | U16 | |
53C3 | 21443 | 1 | RFU | U16 | |
53C4 | 21444 | 1 | Datasize | U16 | |
53C5 | 21445 | 1 | Modbus Fonction | U16 | |
53C6 | 21446 | 1 | Alarm info (alarm, up, down) | U16 | |
53C7 | 21447 | 2 | RFU | U32 | |
53C9 | 21449 | 125 | data read 8 | ByteField | |
5446 | 21574 | 2 | RFU | U32 | |
5448 | 21576 | 2 | last payload timestamp | DATETIME | |
544A | 21578 | 1 | Identification of sensor Modbus frame | U16 | |
544B | 21579 | 1 | Slave address | U16 | |
544C | 21580 | 1 | RFU | U16 | |
544D | 21581 | 1 | Datasize | U16 | |
544E | 21582 | 1 | Modbus Fonction | U16 | |
544F | 21583 | 1 | Alarm info (alarm, up, down) | U16 | |
5450 | 21584 | 2 | RFU | U32 | |
5452 | 21586 | 125 | data read 9 | ByteField | |
54CF | 21711 | 2 | RFU | U32 | |
54D1 | 21713 | 2 | last payload timestamp | DATETIME | |
54D3 | 21715 | 1 | Identification of sensor Modbus frame | U16 | |
54D4 | 21716 | 1 | Slave address | U16 | |
54D5 | 21717 | 1 | RFU | U16 | |
54D6 | 21718 | 1 | Datasize | U16 | |
54D7 | 21719 | 1 | Modbus Fonction | U16 | |
54D8 | 21720 | 1 | Alarm info (alarm, up, down) | U16 | |
54D9 | 21721 | 2 | RFU | U32 | |
54DB | 21723 | 125 | data read 10 | ByteField | |
5558 | 21848 | 2 | RFU | U32 |