The Gateway needs a dedicated IP address on the same VLAN as the Modbus automate. It can be set up as DHCP or static IP.
The default configuration is static IP:
address:
192.168.1.100
netmask:
255.255.255.0
gateway:
192.168.1.1
The Gateway should be synchronized to a NTP server in order to have valid timestamps of the Lora payload.
The default NTP servers configured are 0.pool.ntp.org and 1.pool.ntp.org, however this won't be valid if the Gateway doesn't have internet access.
...
There are no specific operation to do to add a new sensor for BACnet. You can use the Online support interface (https://app.uwiotys.com/index.php/device/list ) to create your infrastructure.
Only Analog input (AI) and Analog values (AV) are currently supported.
...
If your server miss the request, all the data sent can be retrieve using the FTP in /uwiotys/log/uwiotys_functionnal.log
ou or using the data logger CSV output.
...