  • FTP interface for:

    • Management of the device fleet

    • Configuration of outputs

    • Support

  • Web Interface for:

    • Network configuration

    • Lora LoRa Downlink management

    • Support

...

The Gateway needs a dedicated IP address on the same VLAN as the Modbus automate. It can be set up as DHCP or static IP.
The default configuration is static IP:

  • address: 192.168.1.100

  • netmask: 255.255.255.0

  • gateway: 192.168.1.1

The Gateway should be synchronized to a NTP server in order to have valid timestamps of the Lora payload.
The default NTP servers configured are 0.pool.ntp.org and 1.pool.ntp.org, however this won't be valid if the Gateway doesn't have internet access.

...

To read float, see an exemple at FAQ.

...

BACnet

µWiotys supports BACnet protocol (from version 3.4.0).

...

There are no specific operation to do to add a new sensor for BACnet. You can use the Online support interface (https://app.uwiotys.com/index.php/device/list ) to create your infrastructure.

Only Analog input (AI) and Analog values (AV) are currently supported.

...